1
The 2018 Washington State Energy Code (WSEC) section R402.4.1.2
requires air leakage testing for all new houses and additions (see code text
below). The requirement is met if the structure has a leakage rate of 5 air
changes per hour when depressurized with a blower door to 50 Pascals or
less (5ACH
50
). A Pascal is a measurement of pressure. 249 Pascals are
equal to a 1-inch column of water. The test must be performed using a
blower door device consisting of a large fan, frame and panel. A
manometer (pressure gauge) is used to read house and fan pressures.
WSEC states that the test may be performed at any time after rough in.
All penetrations in the building envelope must be sealed including those
for utilities, plumbing, electrical, ventilation and combustion appliances.
The code also states that the test shall be conducted by an approved
third party when required by the building official.
To conduct the test:
1. Close all windows, doors and fireplace and stove doors.
2. Close all dampers including exhaust, intake, make-up air, backdraft
and flue dampers. Since you will be depressurizing the house, dampers in bath fans, etc. will be
sucked closed during the test and will therefore not negatively affect the results.
3. Make sure plumbing traps are filled with water.
4. Leave doors between heated areas open.
5. Open access hatches to conditioned attics and/or conditioned crawl spaces. Leave hatches
closed if these are unconditioned areas.
6. Seal exterior openings for continuously operating ventilation systems and heat recovery
ventilators.
7. Turn off heating and cooling systems but do not seal supply or return registers.
8. Adjust all combustion appliances so that they do not turn on during the test.
9. Install the blower door in an exterior door opening and connect hoses from the manometer to the
blower door fan and the exterior pressure tap. See manufacturer’s instructions for correct set-up.
10. Depressurize the house to -50 Pascals.
11. Record the flow rate (with simple manometers, the fan pressure (Pa) is converted to CFM
50
using a flow table. Many digital manometers sold with blower doors can automatically perform
this conversion, and display
CFM
50
directly. Consult blower door and manometer manuals.
You must now convert the flow rate (CFM
50
) to ACH
50
. Use the following formula:
ACH
50
= (CFM50 X 60) / Volume
Where: ACH
50
= air changes per hour at -50 Pascals
CFM
50
x 60 = converts cubic feet per minute to cubic feet per hour
Volume = conditioned floor area of housing unit multiplied by ceiling height of
8.5 feet (per 402.4.1.2 Testing)